Interstitial condensation in walls and roofs

Warm indoor air carries water vapour, which diffuses outwards through the construction. If it meets a layer that is too cold, it condenses. This interstitial condensation can rot timber and reduce the performance of insulation.

How it works

Every layer resists vapour a little. This is expressed as the sd-value (equivalent air layer thickness, in metres): sd = μ · d, with μ the vapour diffusion resistance factor. Meanwhile the temperature drops through the construction, and so does the saturation vapour pressure. Where the vapour pressure reaches saturation, condensation forms (the dew point).

The Glaser method

EN ISO 13788 uses the same principle with monthly climate data instead of two seasons.

Example: insulated lining on a solid wall

100 mm glass wool on the inside of a masonry wall without a vapour control layer: about 7 kg/m² of condensate per winter according to Glaser, far too much. With a vapour retarder of sd 10 m on the warm side: no condensate.

For internal insulation on capillary-active masonry, Glaser is not suitable above R = 1.0 m²·K/W. Use WTA 6-4 or a dynamic hygrothermal simulation instead.

Rules of thumb

Isolator is a free, independent alternative to established building-physics calculators such as Ubakus: build your wall, roof or floor layer by layer and instantly see the U-value, condensation risk and summer performance – no account, right in your browser. What sets Isolator apart: compare variants side by side to see which build-up performs best, check them straight against building regulations and calculate with the λ-values that apply in your country.