Calculator › Phase shift and damping: summer heat under the roof
Phase shift and damping: summer heat under the roof
A well-insulated roof can still let rooms overheat in summer. Two figures describe how a construction deals with heat: the phase shift (time lag) and the temperature amplitude damping.
What the figures mean
- Phase shift (hours): how much later the peak temperature reaches the inner surface than outside. At 10 hours or more, the midday heat arrives in the evening or at night, when you can ventilate.
- Temperature amplitude damping: how much smaller the swing inside is than outside. A damping of 10 means a ten times smaller swing. Its inverse is the TAV or decrement factor.
Both are calculated according to EN ISO 13786 for a daily temperature wave on the outside.
Example: pitched roof with 200 mm insulation
| Insulation between rafters | Phase shift | Damping |
|---|---|---|
| Glass wool (light) | 7.2 h | 6.2 |
| Wood fibre (heavier, high heat capacity) | 10.7 h | 10.9 |
Same build-up with plasterboard, vapour retarder and wood fibre sarking board. Wood fibre insulates slightly less (λ 0.038) but stores much more heat, which clearly delays the heat.
What helps most against overheating
- External shading of windows: by far most heat enters through glass.
- Night ventilation to remove stored heat.
- Mass and phase shift in roof and walls, especially for attic rooms.
Isolator is a free, independent alternative to established building-physics calculators such as Ubakus: build your wall, roof or floor layer by layer and instantly see the U-value, condensation risk and summer performance – no account, right in your browser. What sets Isolator apart: compare variants side by side to see which build-up performs best, check them straight against building regulations and calculate with the λ-values that apply in your country.