Calculator › How to calculate the R-value (thermal resistance)

How to calculate the R-value (thermal resistance)

The R-value tells you how well a construction resists heat flow. The higher the R-value, the better the insulation. You calculate it from the thickness and thermal conductivity (λ) of each layer.

The formula

Calculate the thermal resistance R of every layer, then add the layers up:

R = d / λ   ·   R = R1 + R2 + … + Rn

Worked example: solid wall with external insulation

LayerThicknessλ (W/m·K)R = d/λ (m²·K/W)
Gypsum plaster10 mm0.510.02
Sand-lime brick150 mm0.990.15
Graphite EPS160 mm0.0325.00
Synthetic render8 mm0.700.01
R of the layers5.18

Almost all of the insulating value comes from the EPS layer; the masonry and render hardly count.

Common mistakes

Typical requirements

In the Netherlands new walls need Rc ≥ 4.7 m²·K/W, roofs 6.3 and floors 3.7. Belgium and Germany set U-values instead (for example U ≤ 0.24 W/m²·K for walls). Always check the rules that apply to your project.

Isolator is a free, independent alternative to established building-physics calculators such as Ubakus: build your wall, roof or floor layer by layer and instantly see the U-value, condensation risk and summer performance – no account, right in your browser. What sets Isolator apart: compare variants side by side to see which build-up performs best, check them straight against building regulations and calculate with the λ-values that apply in your country.