Calculator › How to calculate a U-value

How to calculate a U-value

The U-value (thermal transmittance) is the heat flow through one square metre of construction per degree of temperature difference. The lower the U-value, the better the insulation.

The formula

U = 1 / RT   ·   RT = Rsi + ΣR + Rse

U is in W/(m²·K). ΣR is the sum of the layers (see how to calculate the R-value). Rsi and Rse are the internal and external surface resistances (EN ISO 6946):

Heat flowExampleRsiRse
HorizontalWall0.130.04
UpwardsRoof0.100.04
DownwardsFloor0.170.04

With a ventilated façade or a tiled roof, Rse = Rsi and the layers outside the ventilated cavity are ignored.

Worked example

The externally insulated wall from the R-value example has ΣR = 5.18 m²·K/W:

RT = 0.13 + 5.18 + 0.04 = 5.35  →  U = 1 / 5.35 = 0.19 W/(m²·K)

Corrections

Typical requirements

Belgium (EPB): U ≤ 0.24 W/(m²·K) for walls, roofs and floors. Germany (GEG, when renovating): U ≤ 0.24 for external walls and pitched roofs, 0.20 for flat roofs. Passive house guideline: U ≤ 0.15.

Isolator is a free, independent alternative to established building-physics calculators such as Ubakus: build your wall, roof or floor layer by layer and instantly see the U-value, condensation risk and summer performance – no account, right in your browser. What sets Isolator apart: compare variants side by side to see which build-up performs best, check them straight against building regulations and calculate with the λ-values that apply in your country.