Calculator › Loft insulation: between or over the joists?
Loft insulation: between or over the joists?
If you do not use the loft as a room, insulating the loft floor is usually the cheapest and most effective upgrade in the whole house: less area to insulate, and you stop heating the attic. The only question is where the insulation goes.
Worked example: timber loft floor
Plasterboard ceiling under timber joists (71 mm wide, 600 mm centres, 200 mm deep) with 18 mm floorboards on top. The loft above is unheated and ventilated.
| Option | U (W/m²·K) | Rc (m²·K/W) | Condensation (Glaser) |
|---|---|---|---|
| Uninsulated | 1.66 | 0.40 | – |
| 200 mm glass wool between joists, no vapour control | 0.21 | 4.61 | 4.4 kg/m², floorboards far too wet |
| 200 mm between joists + vapour control layer sd 2 m | 0.21 | 4.61 | 0.33 kg/m², dries out in 25 days |
| 100 mm glass wool on top of the boards | 0.29 | 3.25 | none |
| 200 mm glass wool on top of the boards | 0.16 | 6.11 | none |
| 200 mm blown cellulose on top | 0.18 | 5.39 | none |
Open the over-joist example in the calculator →
Open the between-joist example →
Between the joists: you need a vapour control layer
If you insulate between the joists and keep the boards on top, the boards end up on the cold side. Warm, moist air from the house diffuses up through the ceiling and the insulation and condenses under the boards. Without vapour control that is 4.4 kg of water per m² per winter in this example, and the timber gets far too wet. A vapour control layer on the warm side, directly above the ceiling, solves it.
- The membrane belongs against the ceiling, under the insulation. With an existing ceiling that means taking it down, or laying a membrane between the joists from above and sealing it carefully to the joists.
- Replacing the boards with OSB or chipboard does not help: that is even more vapour-tight on the cold side.
Over the joists: simple and moisture-safe
If the loft is only used for storage, or not at all, lay the insulation on top. Nothing vapour-tight sits on the cold side, so moisture escapes into the ventilated loft. Even without a membrane the calculation shows no condensation, and you can insulate deeper than the joists allow: 200 mm of glass wool reaches U 0.16. To keep a walkway, raise it on battens or use loft legs so the insulation is not compressed.
Requirements
Building regulations differ per country, so check the limit that applies to you. For reference: the Netherlands asks Rc ≥ 2.1 for a roof or loft floor in a renovation, Germany U ≤ 0.24 (and makes loft insulation compulsory in many cases), Belgium U ≤ 0.24. All insulated options above meet those values, except 100 mm on top in Germany and Belgium.
Things to watch
- The loft hatch is often the biggest leak. Insulate it and fit a draught seal.
- Keep the loft ventilated. After insulating, the loft gets colder; without ventilation condensation can form under the roof covering.
- Pipes and tanks in the loft end up on the cold side: insulate them against frost.
- Penetrations (pipes, cables, downlights) must be sealed airtight. Recessed downlights punch holes in the vapour control layer.
In the calculator choose the type Attic floor with Unheated attic. For insulation between joists, tick Inhomogeneous layer and enter the joist width and spacing.
Isolator is a free, independent alternative to established building-physics calculators such as Ubakus: build your wall, roof or floor layer by layer and instantly see the U-value, condensation risk and summer performance – no account, right in your browser. What sets Isolator apart: compare variants side by side to see which build-up performs best, check them straight against building regulations and calculate with the λ-values that apply in your country.