Calculator › Timber frame wall: U-value and vapour control
Timber frame wall: U-value and vapour control
Timber frame is popular for new homes, extensions and tiny houses: light, fast and easy to insulate. But the studs cost insulation value, and a mistake in the layer order causes moisture damage you only notice years later.
Worked example: breathable timber frame wall
Inside to outside: plasterboard, vapour control layer (sd 10 m), glass wool (λ 0.032) between 38 mm studs at 600 mm centres, vapour-open cement fibre sheathing, breather membrane, ventilated cavity and timber cladding.
| Build-up | U (W/m²·K) | Rc (m²·K/W) |
|---|---|---|
| 140 mm studs | 0.25 | 3.81 |
| 184 mm studs | 0.19 | 4.97 |
| 184 mm studs + 60 mm wood fibre board outside | 0.15 | 6.43 |
The cladding and cavity do not count: behind a well-ventilated cavity the calculation stops.
Open this example in the calculator →
The studs cost 15 %
Calculate the 184 mm as if there were no studs and you get Rc 5.84. With studs it is 4.97: 15 % less, while timber covers only 6 % of the area. In reality there is even more timber (sole and head plates, studs around openings). A continuous layer of wood fibre board outside covers the studs and recovers most of that loss.
Tight inside, open outside
The key rule for every timber wall: the inside must be much more vapour-tight than the outside. Any moisture that does get in must be able to escape outwards.
| Variant (184 mm) | Condensation (Glaser) | Drying reserve |
|---|---|---|
| VCL sd 10 m, vapour-open sheathing | none | 1926 g/(m²·a) |
| Smart (variable) membrane, vapour-open sheathing | none | 2077 g/(m²·a) |
| VCL sd 10 m, OSB sheathing outside | none | 1063 g/(m²·a) |
| No vapour control | 4.6 kg/m², fails | – |
| OSB inside and outside, no membrane | 1.7 kg/m², OSB too wet | – |
- Without vapour control 4.6 kg of water per m² condenses against the outer board every winter.
- OSB on both sides looks neat (OSB does restrict vapour), but the outer board restricts almost as much. Moisture can no longer get out.
- The drying reserve (DIN 68800-2) shows how much unplanned moisture, for example from an air leak, the wall can lose per year. Walls need at least 100 g/(m²·a). With vapour-open sheathing the reserve is almost twice as large as with OSB.
Requirements
Limits differ per country, so check your national building regulations. For reference: new-build walls in the Netherlands need Rc ≥ 4.7, so 184 mm studs; Belgium asks U ≤ 0.24, and Germany U ≤ 0.24 when an existing wall is upgraded; 140 mm (U 0.245) just misses that.
Practical tips
- Airtightness matters more than the sd value of the membrane. Tape every joint and junction with the system tape and use grommets at penetrations.
- Service zone. A 30–50 mm batten zone inside the membrane keeps cables and sockets out of the airtight layer. You may insulate it, but keep at most about a quarter of the total thermal resistance on the warm side of the membrane.
- Cladding always ventilated, with a cavity of at least 20 mm and openings top and bottom (with insect mesh).
In the calculator choose Wall. On the insulation layer tick Inhomogeneous layer and enter the stud width and spacing. For timber walls the moisture check also shows the drying reserve to DIN 68800-2.
Isolator is a free, independent alternative to established building-physics calculators such as Ubakus: build your wall, roof or floor layer by layer and instantly see the U-value, condensation risk and summer performance – no account, right in your browser. What sets Isolator apart: compare variants side by side to see which build-up performs best, check them straight against building regulations and calculate with the λ-values that apply in your country.