Calculator › Cavity wall insulation: what U-value do you get?
Cavity wall insulation: what U-value do you get?
Most UK homes built between the 1920s and 1990s have cavity walls, and many cavities are still empty. Filling them is one of the cheapest insulation measures. Here is what it does to the U-value, and when it is not a good idea.
Open the free calculator →Calculate U-value, condensation and summer performance instantly – free, no accountWorked example
Plastered concrete block inner leaf (100 mm, 1200 kg/m³), a 50 mm cavity with open perpends, and a brick outer leaf (102.5 mm).
| Situation | U (W/m²K) | Part L (0.55) |
|---|---|---|
| Empty cavity, 50 mm | 1.86 | – |
| 50 mm blown mineral wool (λ 0.041) | 0.60 | not quite |
| 50 mm EPS beads (λ 0.042) | 0.61 | not quite |
| 65 mm EPS beads | 0.50 | yes |
| 75 mm EPS beads | 0.45 | yes |
| 100 mm EPS beads | 0.35 | yes |
| Aircrete inner leaf (λ 0.16), 50 mm beads | 0.47 | yes |
Heat loss through the wall drops by about two thirds. The inner leaf matters too: with aircrete blocks the empty wall is already at 0.96, and the filled wall reaches 0.47.
We use the design λ for an existing cavity filled afterwards (0.041–0.042). Product data sheets often show a lower declared value, which applies to the material itself but not to an imperfectly filled old cavity.
Open this example in the calculator →
The cavity width decides the result
You can only fill the space that is there. Every 10 mm of EPS beads adds about 0.24 m²K/W. A 50 mm cavity ends up around U 0.60, a 75 mm cavity around 0.45. A reputable installer will drill a test hole or use a borescope to check the width and condition first.
What Part L asks for (England)
Providing cavity wall insulation counts as renovating a thermal element. Approved Document L vol. 1, table 4.3 sets an improved U-value of 0.55 for walls with cavity insulation, for walls currently worse than 0.70. If a narrow cavity cannot reach 0.55, paragraph 4.13 accepts the lowest U-value that is technically feasible and pays back within 15 years: filling the full cavity is then normally what is expected. Grants and the conditions attached change often; check the current schemes before you sign.
When cavity wall insulation goes wrong
- Wind-driven rain. After filling, the outer leaf gets colder and wetter. In exposed locations (western and coastal areas, hills) water can track across the fill to the inner leaf. Check your exposure and the condition of the brickwork: sound pointing, no cracks, working gutters.
- Rubble in the cavity. Mortar droppings bridge the cavity and carry moisture inwards. Have the cavity inspected first.
- Condensation. The Glaser method (DIN 4108-3) shows about 1.2 kg/m² of condensation against the outer leaf in winter, which dries out again in summer. For a wall with a masonry outer leaf DIN 4108-3 does not require this check; the real risk is rain from outside, not vapour from inside.
- Ventilation. Never block air bricks for a suspended floor, or trickle vents.
- Cold bridges at lintels and around openings are not solved by filling the cavity.
In the calculator choose Wall, add the layers and compare the empty cavity (air layer, slightly ventilated) with a filled cavity. You see the U-value and the condensation check straight away.
Isolator is a free, independent alternative to established building-physics calculators such as Ubakus: build your wall, roof or floor layer by layer and instantly see the U-value, condensation risk and summer performance – no account, right in your browser. What sets Isolator apart: compare variants side by side to see which build-up performs best, check them straight against building regulations and calculate with the λ-values that apply in your country.