Calculator › Flat roof U-value: how much insulation do you need?
Flat roof U-value: how much insulation do you need?
A flat roof is almost always insulated on top of the deck: the warm roof. Insulating between the joists (a cold roof) looks easier but often causes hidden moisture damage. Below are worked U-values for concrete and timber roofs, and what Part L asks for.
Open the free calculator →Calculate U-value, condensation and summer performance instantly – free, no accountWarm roof or cold roof?
- Warm roof: a vapour control layer on the deck, insulation boards on top, then the new waterproofing. The deck stays warm and dry. This is the standard solution.
- Cold roof: insulation between the joists, under the deck. The deck and the waterproofing are on the cold side. Felt, EPDM and GRP are almost vapour-tight, so moisture that gets into the roof can hardly get out.
Timber flat roof
Example: plasterboard ceiling, timber joists 47 mm wide at 400 mm centres, an 18 mm OSB deck and a bituminous membrane.
| Build-up | U (W/m²K) | Part L |
|---|---|---|
| Uninsulated | 1.74 | – |
| Warm roof, 100 mm PIR (λ 0.023) | 0.20 | not enough |
| Warm roof, 120 mm PIR | 0.17 | not enough |
| Warm roof, 140 mm PIR | 0.15 | meets 0.16 and 0.15 |
| Warm roof, 150 mm PIR | 0.14 | meets 0.16 and 0.15 |
Open this example in the calculator →
Concrete flat roof
Example: 200 mm reinforced concrete deck with a bituminous membrane.
| Build-up | U (W/m²K) |
|---|---|
| Uninsulated | 3.93 |
| Warm roof, 160 mm EPS (λ 0.036) | 0.21 |
| Warm roof, 120 mm PIR (λ 0.023) | 0.18 |
| Warm roof, 150 mm PIR | 0.15 |
The concrete itself adds almost nothing: nearly all of the U-value comes from the insulation board.
Open the concrete roof example →
Why a cold roof is risky
Fill the same timber roof with 150 mm glass wool between the joists, with a vapour control layer (sd 10 m) below. The U-value is 0.27 and the Glaser method (DIN 4108-3) finds only 0.11 kg/m² of condensation per winter. That looks fine.
But Glaser only looks at vapour diffusing through the materials. In practice moisture also gets in through gaps in the vapour control layer and as built-in moisture. The German timber standard DIN 68800-2 therefore asks for a drying reserve of at least 250 g/(m²·a) for timber roofs: the roof must be able to lose that much extra moisture per year. This cold roof reaches only 14 g/(m²·a). The deck can rot without anyone seeing it. In the UK, BS 5250 also advises against unventilated cold flat roofs unless they are specifically designed.
What Part L asks for (England)
- Re-roofing an existing roof: replacing the waterproofing over more than half of the roof counts as renovation. The whole roof should then reach U 0.16 (Approved Document L vol. 1, table 4.3), if it is technically feasible and pays back within 15 years. If upstands or the structure limit the thickness, a lesser standard may be accepted.
- New roof on an existing home (extension): U 0.15 (table 4.2).
- New dwellings: limiting value 0.16 (table 4.1); the design usually needs better to pass the overall energy calculation.
Wales, Scotland and Northern Ireland have their own regulations with similar but not identical values.
Practical tips
- Upstands and door thresholds. 140 mm of PIR raises the roof by about 15 cm. Check parapets, door thresholds and window sills early.
- Tapered insulation combines fall and insulation. The U-value is then an average; ask the supplier for the calculation.
- Mechanical fixings through the insulation lower the U-value slightly. The calculator can take them into account.
In the calculator choose Flat roof. For timber roofs the moisture check also shows the drying reserve according to DIN 68800-2. There is no UK requirement in the calculator yet; compare the U-value with the figures above.
Isolator is a free, independent alternative to established building-physics calculators such as Ubakus: build your wall, roof or floor layer by layer and instantly see the U-value, condensation risk and summer performance – no account, right in your browser. What sets Isolator apart: compare variants side by side to see which build-up performs best, check them straight against building regulations and calculate with the λ-values that apply in your country.